Rated performance depends on test conditions and system combinations. Check the source notes when selecting equipment or comparing series.
Read original source notes (English)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp. : 27° CDB, 19° CWB, Outdoor temp. : 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20° CDB, Outdoor temp.: 7° CDB, 6° CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
134
seireS
S
VI
VRV
VRV IV S
Series
Read all text from this page and its facing page
PDF page 135
Specifications
Heat Pump
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
Power supply 1-phase, 220-230 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380–415 V, 50 Hz
Btu/h 38,200 47,800 54,600 76,400 81,900
Cooling capacity
kW 11.2 14.0 16.0 22.4 24.0
Btu/h 42,700 47,800 54,600 85,300 88,700
Heating capacity
kW 12.5 14.0 16.0 25.0 26.0
Cooling 2.88 3.83 4.51 5.94 6.88
Power consumption kW
Heating 2.60 3.04 3.59 6.25 6.82
Capacity control % 24 to 100 15 to 100 20 to 100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed swing type Hermetically sealed scroll type
Compressor
Motor output
(Cooling/Heating) kW 1.92 3.2/3.5 3.7 3.8 4.8
Airflow rate m3/min 76 81 80 140
Dimensions (H×W×D) mm 990×940×320 1,430×940×320
Machine weight kg 71 78 80 138
Sound level (Cooling/Heating) dB(A) 52/54 53/54 55/56 57/58 58/59
Cooling °CDB -5 to 46
Operation range
Heating °CWB -20 to 15.5
Type R-410A
Refrigerant
Charge kg 2.9 3.4 4.0 5.8
Liquid 9.5 (Flare) 9.5 (Brazing)
Piping connections mm
Gas 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp. : 27° CDB, 19° CWB, Outdoor temp. : 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Heating: Indoor temp.: 20° CDB, Outdoor temp.: 7° CDB, 6° CWB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXYMQ4AVE RXYMQ5BVM RXYMQ6BVM RXYMQ8AY1 RXYMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
134
seireS
S
VI
VRV
VRV IV S
Series
FACING PAGE — PDF page 134
Outdoor Units
VRV IV S Series
Specifications
Cooling Only
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM RXMQ8AY1 RXMQ9AY1
Power supply 1-phase, 220-230 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380–415 V, 50 Hz
Btu/h 38,200 47,800 54,600 76,400 81,900
Cooling capacity
kW 11.2 14.0 16.0 22.4 24.0
Power consumption kW 2.88 3.83 4.51 5.94 6.88
Capacity control % 24 to 100 15 to 100 20 to 100
Casing colour Ivory white (5Y7.5/1)
Type Hermetically sealed swing type Hermetically sealed scroll type
Compressor
Motor output kW 1.92 3.2 3.7 3.8 4.8
Airflow rate m3/min 76 81 80 140
Dimensions (H×W×D) mm 990×940×320 1,430×940×320
Machine weight kg 71 76 78 131
Sound level dB(A) 52 53 55 57 58
Operation range °CDB -5 to 46
Type R-410A
Refrigerant
Charge kg 2.9 3.4 4.0 5.8
Liquid 9.5 (Flare) 9.5 (Brazing)
Piping connections mm
Gas 15.9 (Flare) 19.1 (Brazing) 22.2 (Brazing)
Notes: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27° CDB, 19° CWB, Outdoor temp.: 35° CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating the installation location and taking soundproofing measures.
• Refrigerant charge is required.
Outdoor unit combinations
MODEL RXMQ4AVE RXMQ5BVM RXMQ6BVM RXMQ8AY1 RXMQ9AY1
kW 11.2 14.0 16.0 22.4 24.0
HP 4 5 6 8 9
Capacity index 100 125 150 200 215
50% 50 62.5 75 100 107.5
Total capacity index
of connectable Combination (%) 100% 100 125 150 200 215
indoor units
130% 130 162.5 195 260 280
Maximum number of connectable indoor units 6 8 9 13 14
Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.